ROFU® MAGNETIC DOOR LOCKING DEVICE
MODEL 8022-002 FOR DOUBLE DOORS

STANDARD FEATURES

Holding Force: 1500 lbs. per side
Easy Installation:
-
Versatile mounting brackets for new and existing doors and frames.
Sensor:
-
Built-in Hall effect crystal affected by door position, voltage input and magnetic field strength.
LED:
-
Red/Green LED door status indicator is attached to magnet housing.
Fail Safe:
-
Releases instantly when power is disconnected.
No residual magnetism.
Fail Alarm: May be released upon activation of fire alarm.
Housing: Attractive, heavy duty, anodized extruded aluminum
Voltage: 12VDC or 24VDC (Field Selectable)
Current Draw:
-
450 mA at 12 VDC per block
225 mA at 24 VDC per block
Mounting hardware included with unit.
Optional Z-Brackets required for in-swinging doors.
Limited Lifetime Warranty

SPECIFICATIONS

Magnet Size: 21" x 2-5/8" x 1-5/8" (LxHxW)
Armature Size: 7-1/4" x 2-3/8" x 5/8" (LxHxW)
Finishes: US28 - Aluminum or US40 - Brown

STANDARD MONITORING FEATURES

Door Status
and
Power Switch

The magnet contains a built - in “C” Form contact 5 Amps @24V that is activated by power to the lock and contact between the armature plate and the surface of the lock. It indicates that the power is on and the door is closed. This feature can be used for remote door surveillance, indicator lights and interlocks.
Secondary Door Status
(as of January 2010 this is  standard on the 8022-002 US28)
A permanent magnet built into the armature place controls a reed switch built into the magnet block.  When installing, make sure the permanent magnet lines up with the reed switch.  When the door is open the switch will advise of the change of status.

OPTIONAL ACCESSORIES

Accessories: Filler Plates, L-Brackets, Glass door mounting aids, Z-Brackets for in-swinging doors, #21033 & Spacers (2 sets)


TYPICAL INSTALLATION ROFU® MODEL 8022-002

Out Swinging doors
-

Inswinging doors
with Z-Bracket

 

  1. ROFU Magnet 8022-002 with door status and tamper switch.
  2. Armature Plate
  3. DC power supply
  4. Access Controls - key switch
  5. Request to exit button
  6. Remote release

 

Switch or solid state switching device

Important: The local on\off switch must be
wired between DC source and magnet
.

Switch or solid state
switching device

Note: Not to scale. Technical Data are subject to change without notice.
Dimensions in Inches and Millimeters.