ROFU® MAGNETIC DOOR LOCKING DEVICE
MODEL 8011-002 FOR SINGLE DOOR










STANDARD FEATURES

Holding Force: 1500 lbs.
Easy Installation:
-
Versatile mounting brackets for new and existing doors and frames.
Sensor:
-
Built-in Hall effect crystal affected by door position, voltage input and magnetic field strength.
LED:
-
Red/Green LED door status indicator is attached to magnet housing.
Fail Safe:
-
Releases instantly when power is disconnected.
No residual magnetism.
Fail Alarm: May be released upon activation of fire alarm.
Housing: Attractive, heavy duty, anodized extruded aluminum
Variable Voltage: 12VDC or 24VDC (Field Adjustable)
Current Draw:
-
450 mA at 12 VDC
225 mA at 24 VDC
Mounting hardware included with unit.
Optional Z-Bracket required for in-swinging doors.
Limited Lifetime Warranty

SPECIFICATIONS

Magnet Size: 10-1/2" x 2-5/8" x 1-5/8" (LxHxW)
Armature Size: 7-1/4" x 2-3/8" x 5/8" (LxHxW)
Finishes: US28 - Aluminum or US40 - Brown
US3 also available, Call for Quote and availability

STANDARD MONITORING FEATURES

Door Status
and
Power Switch

The magnet contains a built - in “C” Form contact 5 Amps @24V that is activated by power to the lock and contact between the armature plate and the surface of the lock. It indicates that the power is on and the door is closed. This feature can be used for remote door surveillance, indicator lights and interlocks.

OPTIONAL ACCESSORIES

Accessories: Filler Plates, L-Brackets, Glass door mounting aids, Z-Brackets for in-swinging doors, #21031 and spacers
Door Status Specify -DS A permanent magnet built into the armature place controls a reed switch built into the magnet block.  When installing, make sure the permanent magnet lines up with the reed switch.  When the door is open the switch will advise of the change of status.


TYPICAL INSTALLATION ROFU® MODEL 8011-002

 

Out Swinging door

 

Inswinging door
with Z-Bracket

 

 

  1. ROFU Magnet 8011-002 with door status and tamper switch.
  2. Armature Plate
  3. DC power supply
  4. Access Controls - key switch
  5. Request to exit button
  6. Remote release

 

Switch or solid state switching device

Important: The local on\off switch must be
wired between DC source and magnet
.

Switch or solid state
switching device

Note: Not to scale. Technical Data are subject to change without notice.
Dimensions in Inches and Millimeters.