ROFU® MAGNETIC DOOR LOCKING DEVICE
MODEL 8011-002 FOR SINGLE DOOR
![]()
|
STANDARD FEATURES |
|
| Holding Force: | 1500 lbs. |
| Easy Installation: - |
Versatile mounting brackets for new and existing doors and frames. |
| Sensor: - |
Built-in Hall effect crystal affected by door position, voltage input and magnetic field strength. |
| LED: - |
Red/Green LED door status indicator is attached to magnet housing. |
| Fail Safe: - |
Releases instantly when power is disconnected. No residual magnetism. |
| Fail Alarm: | May be released upon activation of fire alarm. |
| Housing: | Attractive, heavy duty, anodized extruded aluminum |
| Variable Voltage: | 12VDC or 24VDC (Field Adjustable) |
| Current Draw: - |
450 mA at 12 VDC 225 mA at 24 VDC |
| Mounting hardware included with unit. Optional Z-Bracket required for in-swinging doors. |
|
| Limited Lifetime Warranty | |
|
SPECIFICATIONS |
|
| Magnet Size: | 10-1/2" x 2-5/8" x 1-5/8" (LxHxW) |
| Armature Size: | 7-1/4" x 2-3/8" x 5/8" (LxHxW) |
| Finishes: | US28 - Aluminum or US40 - Brown US3 also available, Call for Quote and availability |
|
STANDARD MONITORING FEATURES |
|
|
Door Status |
The magnet contains a built - in “C” Form contact 5 Amps @24V that is activated by power to the lock and contact between the armature plate and the surface of the lock. It indicates that the power is on and the door is closed. This feature can be used for remote door surveillance, indicator lights and interlocks. |
|
OPTIONAL ACCESSORIES |
|
| Accessories: | Filler Plates, L-Brackets, Glass door mounting aids, Z-Brackets for in-swinging doors, #21031 and spacers |
| Door Status Specify -DS | A permanent magnet built into the armature place controls a reed switch built into the magnet block. When installing, make sure the permanent magnet lines up with the reed switch. When the door is open the switch will advise of the change of status. |
|
TYPICAL INSTALLATION ROFU® MODEL 8011-002 |
|||||
|
|
|||||
|
Out Swinging door |
Inswinging door |
||||
|
|
|||||
|
|
|||||
|
Switch or solid state switching device |
Important: The local on\off switch must be |
Switch or solid state |
|
|
||
|
Note: Not to scale. Technical Data are subject to change
without notice. |
||